In order to maintain proper cooling, the drive must be mounted in a vertical
position (fuses in the upper right hand corner). Refer to Figures 6.1
through 6.3 for the recommended minimum clearance of each drive.
The drive design produces up to a 10°C or 18°F air temperature rise when
the drive is operated at full capacity. Precautions should be taken not to
exceed the maximum inlet ambient air temperature of 55°C (131°F). If the
drive is in an enclosed cabinet, air circulation fans or a closed circuit heat
exchanger may be required. 
	
	
	