What it is
The 3008N is the brain of every Tricon v9.6 (and later) Safety Instrumented System.
Three 3008N units work in Triple-Modular-Redundancy (TMR) inside the same chassis; a two-out-of-three vote guarantees that a single hardware fault never compromises the safety function.
Core technical facts
· Motorola MPC860 32-bit 50 MHz core
· 25 Mbps TriBus for I/O synchronization
· 16 MB DRAM (no battery), 32 KB battery-backed SRAM, 6 MB Flash-PROM
· Consumes only 10 W – stays within the 175 W worst-case power budget of one supply at 60 °C
For quick comparison with earlier MPs, see Table 1.
Table 1 – Main-Processor Evolution
|
Model
|
CPU Speed
|
TriBus
|
DRAM
|
Flash
|
Min. Tricon SW
|
|
3006
|
25 MHz
|
4 Mbps
|
8 MB
|
4 MB
|
v6.x
|
|
3008
|
50 MHz
|
25 Mbps
|
16 MB
|
6 MB
|
v9.0
|
|
3008N
|
50 MHz
|
25 Mbps
|
16 MB
|
6 MB
|
v9.6 (current)
|
Environmental & Mechanical
· Operating: 0 … +60 °C (no derating)
· Storage: –40 … +85 °C
· 5-95 % RH non-condensing
· Shock 15 g / Vibration 1.5 g (5-500 Hz)
Typical applications
Emergency-shutdown (ESD), fire-&-gas, burner-management, turbine protection, HIPPS – anywhere SIL 1-3 is mandatory.
Shipping & Support from PLC Autocontroller
· 20 years of automation sales in Xiamen, China
· Ready-to-ship stock; new & genuine units only
· 12-month functional warranty included
· Express courier (DHL/FedEx) dispatched same day on cleared PO before 3 pm (CN time)
Contact – Sales Manager May
PLC Autocontroller
ab@mooreplc.com
WhatsApp: +86-18106909650
WeChat ID: dcsfcs
Need a quote or have a part-list to check?
Email us the tag list – we will return prices and lead-time within one working day.
What happens next?
-
-
-
Your quote
You’ll get a fully customized quote to fit your unique needs.
-